Standard
-
Rotating electrical machines - Rating and performance.(GB755-2008)
-
Test procedures for three-phase induction motors.(GB1032-2012)
-
Test procedure for direct current machines.(GB1311-2008 )
-
General requirements for safety of small and medium size rotating electrical machines.(GB14711-2006)
-
Standard for hand-over test of electric equipment electric equipment installation engineering.(GB 50150)
-
Code for design of electric distribution of general-purpose utilization equipment.(GB 50055-93)
-
General technical specifications for high voltage test equipments.(DL/T846-2004)
-
Safety requirements for electronic measuring apparatus.(GB4793-1984)
Product Introduction
This product uses electric voltage regulator adjusting voltage. After the booster starts, at a certain rate, up to the rated test values, test time is controlled by the automatic control technology limitless range setting, LED display, End of the test, electric voltage regulator step-down to zero.
Main technical parameters
-
Supply voltage: 220V±5﹪ ; 50Hz/60 Hz±2﹪。
-
Output voltage: 0~35kV; Precision±3﹪
-
Rated capacity: 15KVA
-
Breakdown current: 5mA-1000 mA, Optional setting, continuous adjustable;
-
The time range can be set of test: 1s~9999s, Optional setting, continuous adjustable
-
Alarm Method: Sound and light alarm with Light and warning light
-
Insulation resistance:The insulation resistance of the current input to the frame ≥20MΩ
-
Dielectric strength:Power input on the chassis can withstand 1500V / 50Hz, 1min pressure test, no arc, no breakdown phenomenon
-
Environment temperature:0-40℃
-
Transformer uses high-voltage epoxy Dry-type transformer.
-
This product uses the electric voltage regulator voltage
-
Configuring industrial printer, convenient data storage.
-
The earthing protection device, ensure the safety of test personnel
-
Applicable to 4000V below the machine power frequency voltage withstand test or single line (Forming coil) voltage withstand test
|